CESKO · Busway power distribution systemscaogong@cgbusway.comInternational enquiries · EN

SK-LINE-TT · Track-type Mini Busway

160–1,250 A track-type busway with remote monitoring and communication.

SK-LINE-TT Track-type Mini Busway

SIKE PRODUCT SELECTION MANUAL · 20260917

SK-LINE-TT

160–1,250 A track-type busway with remote monitoring and communication.

Original source: pages 26, 27. Complete selection dimensions, diagrams and technical tables are included below.

Product specifications

Technical specifications
Rated current160, 200, 250, 315, 400, 630, 800, 1000, 1250 A
Applicable standardsIEC 61439-1/6; GB 7251.1/6
SystemAC 3P5W (51); AC 3P5W (53); DC dual circuit
ProtectionIP43 with tap-off; IP54 without tap-off
Operating voltage400 V with end-feed circuit breaker and tap-off; 1000 V without circuit breaker or tap-off
Insulation voltage500 V with end-feed circuit breaker and tap-off; 1000 V without circuit breaker or tap-off
Frequency50/60 Hz
Standard lengths3.0 / 2.4 / 1.8 / 1.2 / 0.6 m; others on request
Support spacing1.5 m
Ambient temperature−5 to +40°C; 24-hour average ≤+35°C
Dimensions, 160–400 A134.5 × 86.6 mm
Dimensions, 630–1250 A153 × 85 mm
GroundingIntegral enclosure or separate copper PE; capacity ≥50% of phase conductor
Busway colorSilver anodized; custom spray colors available
Tap-off box colorSignal Gray RAL 7004; custom colors available
Tap-off box current10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A
Smart functionsRemote monitoring and remote communication
Electrical characteristics · original handbook values
Rated current (A)16020025031540063080010001250
Resistance R20 (mΩ/m)0.3180.2570.1820.1580.1220.0840.0680.6200.540
Reactance X20 (mΩ/m)0.0640.0510.0460.0370.0290.0220.0200.1800.140
Impedance Z20 (mΩ/m)0.3470.2810.2060.1720.1340.0950.0730.6300.540
Voltage drop (V/m), cos φ = 0.80.0810.0920.0750.0810.0800.0870.0920.9000.880

Electrical values are transcribed as printed, including the 1000 A and 1250 A columns. Confirm these columns with the manufacturer before engineering calculations.

Complete technical sheets & dimensions

All original data, drawings and selection tables for this series. Open a page to zoom in. Values and units in the source are preserved.

Model codes, components & installation

See busway and plug-in model codes, structure, joints, installation components and routing dimensions.

Open selection & installation guide

Let’s power your next project.

Discuss your application, layout and power distribution requirements with our team.

Start a conversation