CESKO · Busway power distribution systemscaogong@cgbusway.comInternational enquiries · EN

SK-LINE-L · Nano-aluminum Busway

400–4,000 A nano-aluminum busway.

SK-LINE-L Nano-aluminum Busway

SIKE PRODUCT SELECTION MANUAL · 20260917

SK-LINE-L

400–4,000 A nano-aluminum busway.

Original source: pages 12, 13. Complete selection dimensions, diagrams and technical tables are included below.

Product specifications

Technical specifications
Applicable standardsGB/T 7251.6-2015; IEC 61439-6:2012; EN 61439-6:2012
Rated current400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000 A
ConductorAl + Re + Mn + Mg + Si + Cr
Enclosure6063-T5 aluminum-magnesium alloy
ProtectionIP54 / IP55 / IP65 / IP66
Operating voltage400 V with tap-off; 1000 V without tap-off
Insulation voltage690 V with tap-off; 1000 V without tap-off
Unit length0.5–6 m
Frequency50 Hz
Wiring3P / 4P / 5P; 200% N optional
Withstand voltage8 kV
Insulation resistance≥20 MΩ
Temperature rise≤70 K conductive joints; ≤55 K enclosure
Dielectric strength3.75 kV / 10 s; no breakdown or flashover
Ambient temperature−20 to +40°C
Altitude≤2000 m
Seismic intensity≤Grade 8
Electrical clearance≥10 mm
Creepage distance≥16 mm
Maximum support spacing2 m
InstallationVertical or horizontal
Relative humidityDaily average ≤95%; monthly average ≤90%
Water-vapor pressureDaily average ≤2.2 kPa; monthly average ≤1.8 kPa
Tap-off openingsMinimum one per meter
Electrical characteristics · original handbook values
Rated current (A)4005006308001000125016002000250032004000
Resistance R20 (mΩ/m)0.1220.1130.1030.0950.0620.0460.0380.0320.0250.0180.013
Reactance X20 (mΩ/m)0.0660.0580.0540.0490.0190.0150.0130.0120.0100.0080.007
Impedance Z20 (mΩ/m)0.1400.1390.1390.1000.0750.0580.0420.0330.0280.0190.017
Voltage drop (V/m), cos φ = 0.90.1120.1370.1320.1320.1300.1260.1160.1150.1100.1050.102

Complete technical sheets & dimensions

All original data, drawings and selection tables for this series. Open a page to zoom in. Values and units in the source are preserved.

Model codes, components & installation

See busway and plug-in model codes, structure, joints, installation components and routing dimensions.

Open selection & installation guide

Let’s power your next project.

Discuss your application, layout and power distribution requirements with our team.

Start a conversation