SK-LINE-FS · Cast-resin Busway
400–4,000 A cast-resin busway with IP68 protection.

SIKE PRODUCT SELECTION MANUAL · 20260917
SK-LINE-FS
400–4,000 A cast-resin busway with IP68 protection.
Original source: pages 16, 17. Complete selection dimensions, diagrams and technical tables are included below.
Product specifications
| Applicable standards | GB/T 7251.6-2015; IEC 61439-6:2012 |
|---|---|
| Rated current | 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000 A |
| Enclosure | Mineral-filled synthetic resin |
| Protection | IP68 |
| Operating / insulation voltage | 1000 V / 1000 V |
| Unit length | 0.5–3 m |
| Frequency | 50 Hz |
| Wiring | 3P / 4P / 5P; 200% N optional |
| Withstand voltage | 8 kV |
| Insulation resistance | ≥20 MΩ |
| Temperature rise | ≤70 K conductive joints; ≤55 K enclosure |
| Dielectric strength | 4 kV / 10 s; no breakdown or flashover |
| Ambient temperature | −20 to +40°C |
| Altitude | ≤2000 m |
| Seismic intensity | ≤Grade 8 |
| Electrical clearance | ≥10 mm |
| Creepage distance | ≥16 mm |
| Rated current (A) | 400 | 500 | 630 | 800 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 | 4000 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Resistance R20 (mΩ/m) | 0.132 | 0.112 | 0.097 | 0.076 | 0.050 | 0.037 | 0.031 | 0.023 | 0.018 | 0.014 | 0.012 |
| Reactance X20 (mΩ/m) | 0.395 | 0.036 | 0.066 | 0.060 | 0.055 | 0.043 | 0.036 | 0.032 | 0.025 | 0.019 | 0.013 |
| Impedance Z20 (mΩ/m) | 0.138 | 0.118 | 0.130 | 0.092 | 0.073 | 0.057 | 0.046 | 0.035 | 0.032 | 0.021 | 0.018 |
| Voltage drop (V/m), cos φ = 0.9 | 0.094 | 0.097 | 0.110 | 0.101 | 0.102 | 0.102 | 0.105 | 0.105 | 0.107 | 0.112 | 0.121 |
The conductor entry is printed “Cu+A ≥99.97%” on page 17. Refer to the original sheet and confirm the material designation.