CESKO · Busway power distribution systemscaogong@cgbusway.comInternational enquiries · EN

SK-LINE-DC · DC Busway

400–6,300 A DC distribution with configuration-specific voltage and protection ratings.

SK-LINE-DC DC Busway

SIKE PRODUCT SELECTION MANUAL · 20260917

SK-LINE-DC

400–6,300 A DC distribution with configuration-specific voltage and protection ratings.

Original source: pages 24, 25. Complete selection dimensions, diagrams and technical tables are included below.

Product specifications

Technical specifications
Applicable standardsGB/T 7251.6-2015; IEC 61439-6:2012; EN 61439-6:2012
Rated current400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 5000, 6300 A
ConductorCu + Ag ≥99.97%
Enclosure6063-T5 aluminum-magnesium alloy
Operating voltage250–1500 V without tap-off; 250–1000 V with tap-off; above 1500 V customizable
Protection without tap-offIP54 / IP55 / IP65 / IP66
Protection with tap-offIP54 / IP55
Unit length0.5–6 m
Wiring optionsDC+/DC−; optional 100% N and/or 50% PE as shown in the manual
Electrical clearance≥10 mm at 250–800 V; ≥12 mm at 800–1500 V
Creepage distance≥16 mm at 250–800 V; ≥25 mm at 800–1500 V
Withstand voltage8 kV
Insulation resistance≥20 MΩ
Temperature rise≤70 K conductive joints; ≤55 K enclosure
Dielectric strength3.75 kV / 10 s; no breakdown or flashover
Ambient temperature−20 to +40°C
Altitude≤2000 m
Seismic intensity≤Grade 8
Maximum support spacing2 m
InstallationVertical or horizontal
Relative humidityDaily average ≤95%; monthly average ≤90%
Water-vapor pressureDaily average ≤2.2 kPa; monthly average ≤1.8 kPa
Tap-off openingsMinimum one per meter; double-sided tap-off available

Complete technical sheets & dimensions

All original data, drawings and selection tables for this series. Open a page to zoom in. Values and units in the source are preserved.

Model codes, components & installation

See busway and plug-in model codes, structure, joints, installation components and routing dimensions.

Open selection & installation guide